MONITORAGE DE L'ENERGIE A COURT TERME DANS UN GRAND IMMEUBLE COMMERCIAL.

SHORT-TERM ENERGY MONITORING IN A LARGE COMMERCIAL BUILDING.

Auteurs : BURCH J.

Résumé

ON PEUT UTILISER UN MODELE DE SIMULATION DYNAMIQUE D'UN IMMEUBLE, RENORMALISE A PARTIR DE DONNEES EXPERIMENTALES A COURT TERME, POUR REPONDRE A UNE GRANDE VARIETE DE QUESTIONS SUR LA PERFORMANCE THERMIQUE DE L'IMMEUBLE, TELLES QUE LA MISE EN SERVICE, LA REGULATION DE LA CHARGE ET LE DIAGNOSTIC. ON A APPLIQUE UNE METHODE EXPERIMENTALE A COURT TERME A UN GRAND IMMEUBLE DE BUREAUX POUR ESSAYER LES ETAPES CLES DE LA METHODE DANS UN IMMEUBLE NON RESIDENTIEL. LE MODELE RENORMALISE A PERMIS UNE BONNE CORRELATION AVEC LES DONNEES EXPERIMENTALES ET ON A PU EXPLIQUER LA PERFORMANCE DE L'IMMEUBLE EN TERMES D'ECOULEMENTS DE CHALEUR PHYSIQUEMENT IMPORTANTS. LE RESULTAT LE PLUS IMPORTANT EST QUE LE COEFFICIENT DE PERTE DE L'IMMEUBLE EST 1,9 FOIS PLUS GRAND QUE LA VALEUR DE CONCEPTION, CE QUI EXPLIQUE EN PARTIE POURQUOI LA CONSOMMATION REELLE A ETE CONSIDERABLEMENT PLUS IMPORTANTE QUE LES PREVISIONS.

Détails

  • Titre original : SHORT-TERM ENERGY MONITORING IN A LARGE COMMERCIAL BUILDING.
  • Identifiant de la fiche : 1991-1733
  • Langues : Anglais
  • Date d'édition : 1990
  • Source : Source : ASHRAE Trans.
    vol. 96; n. 1; 1459-1477; 18 fig.; 2 tabl.; 20 ref.