Document IIF

Méthode d’estimation du temps de cycle optimal basée sur les paramètres des refroidisseurs à adsorption.

Method for estimating optimum cycle time based on adsorption chiller parameters.

Auteurs : IGUCHI K., NAKAYAMA M., AKISAWA A.

Type d'article : Article, Article de la RIF

Résumé

The objective of this study is to construct mathematical expressions to estimate the optimum cycle time which maximizes the specific cooling power (SCP) of adsorption chillers with silica gel-water pair. The operating temperature conditions of hot water, cooling water and chilled water, as well as the design parameters such as heat transfer coefficient and heat capacities of the adsorbent heat exchanger and silica-gel, are taken into account to estimate the optimum cycle time. Totally 729 cases were examined to calculate the optimum cycle times from which mathematical expressions were derived. The empirical method reflecting the six parameters successfully estimates the optimum cycle time of the simulations with the coefficient of determination as high as 0.98. The performance for estimating the maximum SCP through the optimum cycle time is even better.

Documents disponibles

Format PDF

Pages : 66-71

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Method for estimating optimum cycle time based on adsorption chiller parameters.
  • Identifiant de la fiche : 30026905
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 105
  • Date d'édition : 09/2019
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2018.10.011

Liens


Voir d'autres articles du même numéro (18)
Voir la source