A diagnostic framework for cfd validation for R-290 dispersion in an indoor heat pump installation room.
Numéro : 0085
Auteurs : BARANWAL A., ESMAEELIAN J., OLTERSDORF T., METHLER T., LAURENZ E., PALM B., SCHNABEL L.
Résumé
The large-scale deployment of heat pumps charged with highly flammable refrigerants, in particular R-290 (propane), creates a growing need for experimentally validated simulation tools to support safe system design. Indoor-mounted configurations are of particular concern because experimental data and validated CFD models are still scarce. This paper presents a diagnostic comparison framework to evaluate agreement between CFD simulations and experimental measurements of propane dispersion following a controlled release in an indoor heat pump installation room. The framework combines three-dimensional, time-resolved CFD concentration fields with measurements from 36 fixed sensors arranged at multiple heights across the room. Spatial reconstruction using Kriging is applied within the convex hull of the bottom-layer sensor positions to enable field-level visualization and comparison at interior grid points across all available CFD timesteps. Field-level residuals are defined as the difference between the Kriging-reconstructed concentration field and the CFD-simulated field at hull-interior grid points. Both methods consistently identify above-LFL propane concentrations throughout the measurement-supported domain during the active release phase, with good agreement on the magnitude and temporal evolution of the flammable mixture volume. Residual diagnostics indicate a modest systematic bias and a spatial structure mismatch attributable to Kriging’s smoothing effect over the sparse sensor network, rather than a fundamental simulation failure. The framework is presented as a transparent diagnostic methodology rather than a data-driven correction pipeline and is intended to guide further CFD model development for flammable refrigerant safety assessment.
Documents disponibles
Format PDF
Pages : 13 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A diagnostic framework for cfd validation for R-290 dispersion in an indoor heat pump installation room.
- Identifiant de la fiche : 30035451
- Langues : Anglais
- Sujet : Technologie
- Source : 17th IIR-Gustav Lorentzen Conference on Natural Refrigerants. Proceedings. Hamilton, New Zealand, August 23-26 2026.
- Date d'édition : 08/2026
- DOI : http://dx.doi.org/10.18462/iir.gl2026.0085
Liens
Voir d'autres communications du même compte rendu (91)
Voir le compte rendu de la conférence
Indexation
- Thèmes : N/A
- Mots-clés : N/A