Absorption de vapeur d'eau par une solution aqueuse de LiBr dans un tube lisse vertical.

Absorption of water vapour by LiBr aqueous solution in a vertical smooth tube.

Auteurs : TAKAMATSU H., YAMASHIRO H., TAKATA N., et al.

Résumé

The water vapour is absorbed by the liquid falling inside a smooth copper tube (16.05 mm i.d., 1200 mm long) that is cooled on its outside with water flowing counter-currently. The presented result includes the effect of solution flow rate, solution subcooling and cooling water temperature on the heat transfer rate, absorption rate and pressure drop in the absorber. Discussion is also presented on the local heat and mass transfer coefficients that are obtained with estimated temperature and concentration at the vapour-liquid interface.

Documents disponibles

Format PDF

Pages : 2001-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Absorption of water vapour by LiBr aqueous solution in a vertical smooth tube.
  • Identifiant de la fiche : 2003-0765
  • Langues : Anglais
  • Source : Thermophysical Properties and Transfer Processes of New Refrigerants.
  • Date d'édition : 03/10/2001

Liens


Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence