Actualisation de la conception de l'émulateur d'environnement thermostatique et évaluation de la méthode d'essai en fonction de la charge.
Thermostat environment emulator design update and assessment for load-based testing methodology.
Numéro : 2522
Auteurs : KIM D., DHILLON P., HORTON W. T., BRAUN J. E.
Résumé
In current testing and rating approaches for estimating seasonal energy efficiency (e.g., SEER) of residential heat-pump systems, the embedded controls of the unit under test (UUT) are overridden. As a result, the rated performance does not fully capture part-load operation and degradation effects that occur due to interaction of the integrated controls, equipment, and building dynamics, and does not incentivize the implementation of improved controllers. To address this deficiency, a load-based testing methodology has been developed for estimating the seasonal performance of residential heat pumps based on their dynamic performance measurement in a lab. The load-based testing methodology emulates the response of building sensible and latent loads to the equipment controls in a psychrometric test chamber by continuously updating the room temperature and humidity based on a virtual building model. The test unit thermostat naturally responds to dynamic temperature variations and controls the equipment capacity in response to a deviation from its setpoint. Since the thermostat response is integral in load-based testing, it is critical to provide representative and reproducible conditions to the thermostat. For this, a thermostat environment emulator (TEE) was developed to provide a standardized environment for the thermostat during load-based tests in order to ensure repeatability and reproducibility. This paper presents an updated design of a thermostat environment emulator that was previously presented by Cheng et al. (2021a) to improve performance and applicability across different test facilities. First, design updates to the TEE are discussed in detail, and then performance assessment results of the TEE are presented. Finally, performance and operation characteristics evaluation results of the TEE are discussed based on load-based tests with a 2-ton variable-speed heat pump.
Documents disponibles
Format PDF
Pages : 11 p.
Disponible
Gratuit
Détails
- Titre original : Thermostat environment emulator design update and assessment for load-based testing methodology.
- Identifiant de la fiche : 30030763
- Langues : Anglais
- Sujet : Technologie
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 2022
Liens
Voir d'autres communications du même compte rendu (224)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Pompes à chaleur à usage domestique
- Mots-clés : Thermostat; Essai; Pompe à chaleur domestique; Performance; Norme; Conception; Chauffage; Conditionnement d'air; Modélisation
-
Effect of a thermostat environment emulator on ...
- Auteurs : DHILLON P., KIM D., HORTON W. T., BRAUN J. E.
- Date : 2022
- Langues : Anglais
- Source : 2022 Purdue Conferences. 19th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
DYNAMIC MODELLING OF A RESIDENTIAL HEAT PUMP FR...
- Auteurs : CRAWFORD R. R., SHIREY D. B.
- Date : 1987
- Langues : Anglais
Voir la fiche
-
Residential vertical geothermal heat pump syste...
- Auteurs : THORNTON J. W., MCDOWELL T. P., SHONDER J. A., HUGHES P. J., PAHUD D., HELLSTROEM G. A. J.
- Date : 1997
- Langues : Anglais
- Source : ASHRAE Transactions.1997 Annual Meeting, Boston, MA.
Voir la fiche
-
Performance test of residential heat pump after...
- Auteurs : IN S., CHO K., LIM B., et al.
- Date : 11/2014
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 72 - n. 2
Voir la fiche
-
Laboratory Load-Based Testing, Performance Mapp...
- Auteurs : CHENG L.
- Date : 2020
- Langues : Anglais
- Formats : PDF
Voir la fiche