Résumé
In a direct expansion (DX) air conditioning (A/C) system having a variable-speed compressor and supply fan, the degree of refrigerant superheat regulated by a built-in conventional proportional-integral-derivative (PID) controller would experience fluctuation, after the speeds of both compressor and supply fan were regulated by a capacity controller. This would impact the operating efficiency and stability of the DX A/C system. Therefore a new DS controller, which was intended for improving the DS control performance when the fluctuation of operating DS was resulted from speed changes, has been developed and its controllability tested. The test results showed that this new DS controller, which replaced the conventional PID DS controller, can significantly improve DS control performance after speed changes while indoor air temperature and humidity were controlled to their respective settings. With the improved DS control performance, the operating efficiency and stability of the DX A/C system were also enhanced.
Documents disponibles
Format PDF
Pages : pp. 125-134
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Improving degree of superheat control in a direct expansion (DX) air conditioning (A/C) system.
- Identifiant de la fiche : 2009-2447
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 1
- Date d'édition : 01/2010
Liens
Voir d'autres articles du même numéro (20)
Voir la source
Indexation
-
Indoor thermal comfort characteristics under th...
- Auteurs : DENG S., LI Z., QU M.
- Date : 08/2009
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 29 - n. 11-12
Voir la fiche
-
UNE REVOLUTION DANS LA CLIMATISATION DE CONFORT...
- Auteurs : PARIS J.
- Date : 06/1991
- Langues : Français
- Source : Rev. gén. Froid - vol. 81 - n. 5
Voir la fiche
-
Inherent operational characteristics and operat...
- Auteurs : XIA Y., DENG S., CHAN M. Y.
- Date : 25/02/2017
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 113
Voir la fiche
-
A novel proportional-derivative (PD) law based ...
- Auteurs : LI Z., XU X., DENG S., et al.
- Date : 09/2015
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 57
- Formats : PDF
Voir la fiche
-
Inherent correlation between the total output c...
- Auteurs : XU X., XIA L., CHAN M., et al.
- Date : 09/2010
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 30 - n. 13
Voir la fiche