Document IIF

Amélioration de la régulation de la surchauffe dans un système de conditionnement d'air à détente directe.

Improving degree of superheat control in a direct expansion (DX) air conditioning (A/C) system.

Auteurs : QI Q., DENG S., XU X., et al.

Type d'article : Article, Article de la RIF

Résumé

In a direct expansion (DX) air conditioning (A/C) system having a variable-speed compressor and supply fan, the degree of refrigerant superheat regulated by a built-in conventional proportional-integral-derivative (PID) controller would experience fluctuation, after the speeds of both compressor and supply fan were regulated by a capacity controller. This would impact the operating efficiency and stability of the DX A/C system. Therefore a new DS controller, which was intended for improving the DS control performance when the fluctuation of operating DS was resulted from speed changes, has been developed and its controllability tested. The test results showed that this new DS controller, which replaced the conventional PID DS controller, can significantly improve DS control performance after speed changes while indoor air temperature and humidity were controlled to their respective settings. With the improved DS control performance, the operating efficiency and stability of the DX A/C system were also enhanced.

Documents disponibles

Format PDF

Pages : pp. 125-134

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Improving degree of superheat control in a direct expansion (DX) air conditioning (A/C) system.
  • Identifiant de la fiche : 2009-2447
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 1
  • Date d'édition : 01/2010

Liens


Voir d'autres articles du même numéro (20)