Document IIF

Amélioration des performances d’une pompe à chaleur aérothermique fonctionnant avec un compresseur rotatif à injection de gaz via un port à ailettes.

Performance improvement of air source heat pump using gas-injected rotary compressor through port on blade.

Auteurs : WANG B., LIU X., SHI W.

Type d'article : Article, Article de la RIF

Résumé

Gas injection has been a crucial technology to avoid the serious degradation of air source heat pumps in low ambient temperature. A novel injection structure on the blade for rotary compressors has been put forward in previous research to overcome the drawback of traditional injection structures. Based on a verified numerical model, the thermodynamic performance of an air source heat pump with the new gas-injected rotary compressor is investigated. The results indicate that, compared to the air source heat pump with the regular single-stage rotary compressor, the proposed injection structure can enhance heating capacity and COP of the air source heat pump by 23.1–28.2% and 4.5–8.1%, respectively.

Documents disponibles

Format PDF

Pages : 91-98

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Performance improvement of air source heat pump using gas-injected rotary compressor through port on blade.
  • Identifiant de la fiche : 30019835
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 73
  • Date d'édition : 01/2017

Liens


Voir d'autres articles du même numéro (21)
Voir la source