ANALYSE D'UN SYSTEME INTEGRE DE CONDITIONNEMENT D'AIR A DESHYDRATANT LIQUIDE ET A ABSORPTION.

ANALYSIS OF AN INTEGRATED ABSORPTION/LIQUID DESICCANT AIR CONDITIONING SYSTEM.

Auteurs : GARI H. A., ALY S. E., FATHALAH K. A.

Type d'article : Article

Résumé

DANS LE RAPPORT, ON PRESENTE UNE ANALYSE D'UNE MACHINE INTEGREE A ABSORPTION, AVEC UN DESHUMIDIFICATEUR A DESHYDRATANT LIQUIDE ACTIONNE PAR DE LA CHALEUR EMISE PAR DE L'EAU, QUE L'ON UTILISE EN CONDITIONNEMENT D'AIR. ON DECRIT UN MODELE MATHEMATIQUE DU GROUPE DE DESHYDRATANT LIQUIDE, ET ON RESOUD LES EQUATIONS DIRECTRICES. ON A APPLIQUE LE MODELE A UNE CHAMBRE DE DESHUMIDIFICATION (CDH) ET A UNE CHAMBRE DE REGENERATION (CRG), SELON UN REGIME COUPLE. LES RESULTATS ONT MONTRE QUE LA TEMPERATURE DE L'EAU DE REFROIDISSEMENT ET LES POTENTIELS DE TRANSFERT SONT LES FACTEURS DE CONTROLE AFFECTANT LA CDH, ALORS QUE LE POTENTIEL DE TRANSFERT DE MASSE ET LE RAPPORT MASSIQUE DE L'AIR ABSORBANT DOMINENT DAN L G. POUR DE L'AIR EXTERIEUR, D'UNE TEMPERATURE DE BULBE SEC/TEMPERATURE DE BULBE HUMIDE DE 315/304 K (42/31 DEG C), LE SYSTEME INTEGRE PRESENTE UN COP GLOBAL ESTIME A 1,21, POUR UNE ALIMENTATION EN EAU CHAUDE A 413 K (140 DEG C) AU A 303 K (30 DEG C). CE COP EST SUPERIEUR DE 50 % A CELUI D'UN GROUPE DE REFROIDISSEMENT A ABSORPTION SEUL (0,81).

Détails

  • Titre original : ANALYSIS OF AN INTEGRATED ABSORPTION/LIQUID DESICCANT AIR CONDITIONING SYSTEM.
  • Identifiant de la fiche : 1991-0317
  • Langues : Anglais
  • Source : Heat Recov. Syst. CHP - vol. 10 - n. 2
  • Date d'édition : 1990