ANALYSE DE LA FORMATION DE GLACE AVEC INVERSION D'ECOULEMENT POUR UNE APPLICATION A UNE POMPE A CHALEUR OU L'EAU EST LA SOURCE DE CHALEUR.

ANALYSIS OF ICE FORMATION WITH FLOW REVERSAL FOR APPLICATION TO A WATER SOURCE HEAT PUMP.

Résumé

ON DEVELOPPE UN MODELE NUMERIQUE DE LA FORMATION DE GLACE EN FAISANT COULER DE L'EAU DANS UNE SECTION ANNULAIRE AILETEE D'UN EVAPORATEUR. IL PREVOIT LES PROFILS DE LA GLACE EN FONCTION DE LA POSITION AXIALE ET DU TEMPS, ET LES VALEURS DE TRANSFERT D'ENERGIE EN FONCTION DU TEMPS. IL PERMET PAR AILLEURS LES INVERSIONS DE LA DIRECTION DES ECOULEMENTS DANS LA SECTION ANNULAIRE. L'INVERSION DE L'ECOULEMENT DEGIVRE LES SURFACES DE L'EVAPORATEUR PARCE QU'ELLE FAIT FONDRE UNE PARTIE DE GLACE OU LA FAIT SE DETACHER DE LA PAROI. AINSI, ON PROPOSE LA METHODE D'INVERSION DES ECOULEMENTS COMME SOLUTION AU DEGIVRAGE, QUI N'ENTRAINE PAS LES PERTES COMMUNEMENT INDUITES PAR LES AUTRES METHODES DE DEGIVRAGE. LES RESULTATS REVELENT UN GAIN IMPORTANT DE TRANSFERT DE L'ENERGIE POUR LE CAS DE L'INVERSION PAR RAPPORT AU TRANSFERT D'ENERGIE OBTENU SANS INVERSION. DANS L'ETUDE, ON PROPOSE UNE TROISIEME SOLUTION QUI CONSISTE A INTERROMPRE INVERSION, AFIN D'OBTENIR UN DETACHEMENT SUPPLEMENTAIRE DE GLACE. LES RESULTATS DE TRANSFERT DE CHALEUR GLOBAL DANS CE CAS SONT TRES SIMILAIRES A CEUX CONCERNANT L'INVERSION SANS INTERRUPTION DE L'ECOULEMENT DU FRIGORIGENE.

Détails

  • Titre original : ANALYSIS OF ICE FORMATION WITH FLOW REVERSAL FOR APPLICATION TO A WATER SOURCE HEAT PUMP.
  • Identifiant de la fiche : 1991-0834
  • Langues : Anglais
  • Date d'édition : 1989
  • Source : Source : ASHRAE Trans.
    vol. 95; n. 2; 366-374; 11 fig.; 2 tabl.; 7 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.