Analyse de la performance d'un système de refroidissement d'hydrure métallique monophasique à quatre lits. B. Influence de la récupération de la chaleur.

Performance analysis of a single-stage four-bed metal hydride cooling system. B. Influence of heat recovery.

Auteurs : ABRAHAM K., PRAKASH MAIYA M., SRINIVASA MURTHY S.

Type d'article : Article

Résumé

The influence of heat recovery on the performance of a single-stage multi-bed metal hydride cooling system was studied with Zr(0.9)Ti(0.1)CrFe and Zr(0.7)Ti(0.3)CrFe as high and low temperature alloys respectively. The heat recovery cycle effectively utilizes the sensible heat contained in the beds at the end of desorption and resorption processes thereby reducing the heat input and increasing the refrigerating effect. Compared with the basic cycle, the COP of heat recovery cycle improves by about 15 to over 75%, depending on the operating temperatures.

Détails

  • Titre original : Performance analysis of a single-stage four-bed metal hydride cooling system. B. Influence of heat recovery.
  • Identifiant de la fiche : 2004-2827
  • Langues : Anglais
  • Source : International Journal of thermal Sciences - vol. 42 - n. 1
  • Date d'édition : 01/2003

Liens


Voir d'autres articles du même numéro (3)
Voir la source