Document IIF
Analyse de la performance d’une pompe à chaleur liquide-eau au R407C: Effet d’un échangeur de chaleur liquide-vapeur et de la production d’eau chaude sanitaire.
Performance analysis of a R407C liquid-to-water heat pump: Effect of a liquid–vapor heat exchanger and domestic hot water production.
Auteurs : ORTEGA I., SIERES J., CERDEIRA F., et al.
Type d'article : Article, Article de la RIF
Résumé
This paper presents an experimental study of a R407C liquid-to-water heat pump for combined space heating (SH) and domestic hot water (DHW) production. The main components of the heat pump are a scroll compressor, a desuperheater for DHW production, two brazed plate heat exchangers (condenser and evaporator) and a thermostatic expansion valve. A liquid–vapor heat exchanger (LVHEx) has been included in order to study its effect on the heat pump performance. Experimental results for typical operating conditions in the heating mode of operation (low and medium temperature applications) are presented and discussed. These operating conditions are combined with simultaneous DHW production at different flow rates and temperature values. Results show that, in general, the COP is higher with simultaneous SH and DHW production than with SH alone. Also, using the LVHEx yields lower heating and compression powers and, in general, slightly lower COP values.
Documents disponibles
Format PDF
Pages : 125-135
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Performance analysis of a R407C liquid-to-water heat pump: Effect of a liquid–vapor heat exchanger and domestic hot water production.
- Identifiant de la fiche : 30025740
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 101
- Date d'édition : 05/2019
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2019.02.024
Liens
Voir d'autres articles du même numéro (17)
Voir la source
Indexation
-
Experimental study of a R407C liquid-to-water h...
- Auteurs : ORTEGA I., SIERES J., CERDEIRA PÉREZ F., et al.
- Date : 09/07/2018
- Langues : Anglais
- Source : 2018 Purdue Conferences. 17th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Bomba de calor con CO2 para agua caliente sanit...
- Auteurs : FORNASIERI E., GIROTTO S., MANCINI F., et al.
- Date : 10/2011
- Langues : Espagnol
- Source : Frío Calor Aire acondicionado - vol. 39 - n. 440
- Formats : PDF
Voir la fiche
-
A carbon dioxide domestic hot water heat pump w...
- Auteurs : FORNASIERI E., GIROTTO S., MANCINI F., et al.
- Date : 12/04/2010
- Langues : Anglais
- Source : 9th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2010). Proceedings. Sydney, Australia, April 12-14, 2010.
- Formats : PDF
Voir la fiche
-
Experimental Evaluation of High Performance Int...
- Auteurs : MILLER W., BERRY R., DURFEE N., et al.
- Date : 11/07/2016
- Langues : Anglais
- Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Influence of the refrigerant charge in an R407C...
- Auteurs : SIERES J., ORTEGA I., CERDEIRA F., et al.
- Date : 02/2020
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 110
- Formats : PDF