Document IIF

Analyse de la performance de deux nouveaux évaporateurs pour un refroidisseur à adsorption à trois adsorbeurs.

The performance analysis of a novel dual evaporator type three-bed adsorption chiller.

Auteurs : MIYAZAKI T., AKISAWA A., SAHA B. B.

Type d'article : Article, Article de la RIF

Résumé

This paper deals with the performance evaluation of an innovative, waste heat driven dual evaporator type three-bed adsorption cycle for cooling application. The innovative adsorption chiller has two evaporators, three adsorbent beds, and a condenser, and the evaporators work at different pressure levels. The effects of hot water inlet temperature, chilled water inlet and outlet temperatures, and cycle time on the specific cooling capacity (SCC) and COP were predicted by simulation. For the same operating condition, the SCC and COP of the dual evaporator type three-bed adsorption chiller were found to be 1.5 and 1.7 times higher than those of the two-bed single-stage adsorption chiller, respectively.

Documents disponibles

Format PDF

Pages : pp. 276-285

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : The performance analysis of a novel dual evaporator type three-bed adsorption chiller.
  • Identifiant de la fiche : 2009-2352
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 33 - n. 2
  • Date d'édition : 03/2010

Liens


Voir d'autres articles du même numéro (21)
Voir la source