To make full utilization of waste heat with large temperature glide, a new absorption refrigeration cycle with a simple construction is proposed. In this cycle, the solution flowing out from a low-pressure and high-temperature absorber absorbs refrigerant vapor in a low-pressure and low-temperature absorber which is cooled by evaporating refrigerant in a high-pressure evaporator. The refrigerant vapor to be absorbed in the low-pressure and low-temperature absorber comes from a low-pressure evaporator. The vapor flowing out from the high-pressure evaporator is absorbed by solution in a high-pressure absorber. This solution sent to a liquid pump comes from a low-pressure and low-temperature absorber. Compared to a single-effect absorption cycle, the molar fraction of refrigerant of the solution into generator is much greater, resulting in drastic temperature decline for the displaced exhaust gas/water of this cycle, which means the new cycle can effectively utilize waste heat with large temperature glide. Theoretical simulation results show that the cooling capacity per unit mass of exhaust gas of the proposed cycle is about 20% higher than that of a single-effect absorption cycle, especially for the situation that temperature of supplied waste heat is lower and/or refrigeration temperature is lower.
Détails
- Titre original : The performance analysis of a novel absorption refrigeration cycle used for waste heat with large temperature glide.
- Identifiant de la fiche : 30017045
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 93
- Date d'édition : 25/01/2016
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2015.10.034
Liens
Voir d'autres articles du même numéro (72)
Voir la source
-
Cooling capacity optimization of a waste heat a...
- Auteurs : WU C.
- Date : 03/1993
- Langues : Anglais
- Source : Heat Recov. Syst. CHP - vol. 13 - n. 2
Voir la fiche
-
Possibilités et limites des installations à sor...
- Auteurs : STOLK A. L.
- Date : 04/1992
- Langues : Néerlandais
- Source : Koude & Luchtbehandeling - vol. 85 - n. 4
Voir la fiche
-
Performance analysis of solution transportation...
- Auteurs : KIANI B., HAMAMOTO Y., AKISAWA A., et al.
- Date : 2003
- Langues : Anglais
- Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 20 - n. 4
Voir la fiche
-
An improved absorption refrigeration system for...
- Auteurs : BAI Y., LU D., LIU Z., GONG M., SHEN J.
- Date : 01/2022
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 133
- Formats : PDF
Voir la fiche
-
Performance evaluation of a lithium-chloride ab...
- Auteurs : OBERWEIS S., AL-SHEMMERI T.
- Date : 10/2012
- Langues : Anglais
- Source : Applied Sciences - n. 4
Voir la fiche