Analyse expérimentale des tubes capillaires adiabatiques.

An experimental analysis of adiabatic capillary tubes.

Auteurs : MELO C., FERREIRA R. T. S., BOABAID NETO C., et al.

Type d'article : Article

Résumé

The investigations, performed on a described facility, include the effect of capillary length, capillary diameter, refrigerant subcooling, condensing pressure and type of refrigerant on the mass flow-rates through the capillaries. The experiments were performed with CFC-12, HFC-134a and HC-600a, and at different condensing pressures and levels of subcooling under choked flow conditions. Eight different capillaries were used, and extensive data (exceeding 1000 sets) were collected. A conventional, dimensional analysis was performed to derive correlations to predict the mass flow rates for different refrigerants. The developed correlations are found to be in good agreement with the measured data.

Détails

  • Titre original : An experimental analysis of adiabatic capillary tubes.
  • Identifiant de la fiche : 2001-0051
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 19 - n. 6
  • Date d'édition : 06/1999

Liens


Voir d'autres articles du même numéro (2)
Voir la source