Analyse expérimentale et numérique d'un système frigorifique à absorption de NH3–H2O à double [effet] et refroidi à l'air.

Experimental and numerical analysis of an air-cooled double-lift NH3–H2O absorption refrigeration system.

Auteurs : APRILE M., TOPPI T., GUERRA M., et al.

Type d'article : Article, Article de la RIF

Résumé

The prototype of an air-cooled double-lift NH3–H2O absorption chiller driven by hot water at low temperature is presented. The main objective of the study is to illustrate the experimental performances of the prototype under different operating conditions. A mathematical model of the cycle is developed, along with a procedure for the identification of otherwise difficult to measure data, with the purpose of providing the complete picture of the internal thermodynamic cycle. The combined experimental and numerical data allowed assessing the effects on the thermodynamic cycle with varying operating conditions. The unit operated steadily with chilled water inlet 12°C, outlet 7°C, air temperature between 22°C and 38°C, and hot water driving temperatures between 80°C and 90°C. The reference cooling capacity at air temperature of 30°C is 2.5 kW, with thermal COP about 0.3 and electrical COP about 10.

Documents disponibles

Format PDF

Pages : 57-68

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental and numerical analysis of an air-cooled double-lift NH3–H2O absorption refrigeration system.
  • Identifiant de la fiche : 30013109
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 50
  • Date d'édition : 02/2015