Document IIF

Analyse théorique d'un système frigorifique à compression de vapeur au R-502, R-404A et R-507A.

Theoretical analysis of a vapour compression refrigeration system with R-502, R-404A and R-507A.

Auteurs : ARORA A., KAUSHIK S. C.

Type d'article : Article, Article de la RIF

Résumé

This paper presents a detailed exergy analysis of an actual vapour compression refrigeration cycle. A computational model has been developed for computing COP, exergy destruction, exergetic efficiency and efficiency defects for R502, R-404A and R-507A. The present investigation has been done for evaporator and condenser temperatures in the range of -50 to 0°C and 40 to 55°C, respectively. The results indicate that R-507A is a better substitute to R-502 than R-404A. The efficiency defect in condenser is highest, and lowest in liquid vapour heat exchanger for the refrigerants considered.

Documents disponibles

Format PDF

Pages : 998-1005

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Theoretical analysis of a vapour compression refrigeration system with R-502, R-404A and R-507A.
  • Identifiant de la fiche : 2008-2452
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 6
  • Date d'édition : 09/2008

Liens


Voir d'autres articles du même numéro (17)
Voir la source