Analyses énergétique et exergétique d'un système solaire intégré de pompe à chaleur.

Energy and exergy analyses of an integrated solar heat pump system.

Auteurs : SULEMAN F., DINCER I., AGELIN-CHAAB M.

Type d'article : Article

Résumé

An integrated solar and heat pump based system for industrial heating is developed in this study. The system comprises heat pump cycle for process heating water and solar energy for another industrial heating process. Comprehensive energy and exergy analyses are performed on the system. These analyses generated some compelling results as expected because of the use of green and environmentally friendly energy sources. The results show that the energy efficiency of the process is 58% while the exergy efficiency is 75%. Energetic COP of the heat pump cycle is 3.54 whereas the exergy efficiency is 42.5%. Moreover, the energetic COP of the system is 2.97 and the exergy efficiency of the system is 35.7%. In the parametric study, a different variation such as changing the temperature and pressure of the condenser also shows positive results.

Détails

  • Titre original : Energy and exergy analyses of an integrated solar heat pump system.
  • Identifiant de la fiche : 30014827
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 73 - n. 1
  • Date d'édition : 12/2014
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2014.08.006

Liens


Voir d'autres articles du même numéro (44)
Voir la source