APPLICATION D'UN SYSTEME FRIGORIFIQUE A DESHYDRATANT POUR LES SUPERMARCHES.

APPLICATION OF A DESICCANT COOLING SYSTEM TO SUPERMARKETS.

Auteurs : CALTON D. S.

Résumé

UNE ANALYSE EN SERVICE REEL D'UN SYSTEME DE CHAUFFAGE, VENTILATION, CONDITIONNEMENT D'AIR AVEC DESHYDRATANT MONTRE QU'UN ABAISSEMENT DES DEBITS D'AIR D'ENVIRON 9 M3/H PAR M2 DE ZONE DE VENTE EST POSSIBLE. ON A EMPLOYE UNE STRATEGIE DE REPARTITION D'AIR FOURNISSANT LES 2/3 DE L'AIR A L'AVANT DU MAGASIN ET RAMENANT L'AIR SOUS LES MEUBLES FRIGORIFIQUES. L'ABAISSEMENT DE L'HUMIDITE RELATIVE DU MAGASIN A 40 % A FAIT APPARAITRE UNE REDUCTION DE LA CHARGE DES MEUBLES FRIGORIFIQUES ET DE LA FORMATION DE GIVRE. L'ENSEMBLE DU SYSTEME MONOBLOC UTILISE LA RECUPERATION DE CHALEUR DES GROUPES FRIGORIFIQUES COMPRESSEURS-CONDENSEURS POUR LE CHAUFFAGE DU MAGASIN EN HIVER. L'AIR DE REGENERATION PAR DESHYDRATANT EST CHAUFFE AU PREALABLE EN RECUPERANT UNE PARTIE DE LA CHALEUR REJETEE PAR LES GROUPESCOMPRESSEURS-CONDENSEURS DE CONDITIONNEMENT D'AIR.

Détails

  • Titre original : APPLICATION OF A DESICCANT COOLING SYSTEM TO SUPERMARKETS.
  • Identifiant de la fiche : 1986-1621
  • Langues : Anglais
  • Date d'édition : 1985
  • Source : Source : ASHRAE Trans.
    vol. 91; n. 1B; 441-446; 4 tabl.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.