Augmentation des performances d'un système de refroidisseur d'eau utilisant des nanofrigorigènes.

Performance augmentation of a water chiller system using nanofluids.

Auteurs : LIU M. S., LIN M. C. C., HU R., et al.

Résumé

This study examined the overall system performance of a water chiller that is subject to the influence of nanofluids. The system performance of a 10 RT water chiller (air conditioner) located in a well-controlled chamber was observed. Multiwalled carbon nanotubes were used as the heat transfer medium in the evaporator. The system performance was tested at the standard water chiller rating condition in the range of the flow rate (60 to 140 L/min). The static measurement of the thermal conductivity of the nanofluids showed only a 1.3% marginal increase relative to the base fluid, so it was surprising to find that a 4.2% increase in cooling capacity and a slight decrease of about 0.8% in power consumption occurred in the nanofluids system at a flow rate of 100 L/min. In summary, with the introduction of nanofluids, the COP of the water chiller is increased by 5.15% relative to that without nanofluids.

Détails

  • Titre original : Performance augmentation of a water chiller system using nanofluids.
  • Identifiant de la fiche : 2009-2460
  • Langues : Anglais
  • Source : ASHRAE Transactions. Papers presented at the 2009 ASHRAE Winter Conference: Chicago, Illinois, January 2009. Volume 115, part 1.
  • Date d'édition : 25/01/2009