AVANTAGES ET LIMITES DE LA METHODE DE CONTRE-VERIFICATION "THORP", POUR LA PERFORMANCE D'UN GROUPE REFROIDISSEUR D'EAU.

ADVANTAGES AND LIMITATIONS OF THE THORP METHOD OF CROSS-CHECKING WATER CHILLER PERFORMANCE.

Auteurs : BAILEY-MCEWAN M.

Résumé

LORSQU'ON EVALUE LA PERFORMANCE D'UNE MACHINE, ON CONSIDERE EN GENERAL QUE LES RESULTATS SONT ACCEPTABLES S'ILS DONNENT UN BILAN THERMIQUE ACCEPTABLE. SI LE BILAN THERMIQUE N'EST PAS ACCEPTABLE, ON A RECOURS A UNE CONTRE-VERIFICATION, CONNUE SOUS LE NOM DE < METHODE THORP > (QUI EST BASEE SUR L'EVALUATION INDEPENDANTE DU COP A PARTIR DE MESURES DANS LE CIRCUIT DE FRIGORIGENE) ; IL S'AGIT D'ESSAYER D'IDENTIFIER L'ERREUR LA PLUS IMPORTANTE. AVEC LES GROUPES REFROIDISSEURS D'EAU CENTRIFUGES, CETTE METHODE NE PEUT ETRE UTILISEE QUE S'IL N'Y A PAS DE DERIVATION DE GAZ CHAUDS AFIN DE MAINTENIR LA STABILITE DE FONCTIONNEMENT DU COMPRESSEUR. MALHEUREUSEMENT, LA METHODE < THORP > NE DETECTE PAS TOUTES LES CATEGORIES D'ERREURS NON ACCEPTABLES, AUSSI NE PEUT-ON JAMAIS PROUVER L'ABSENCE TOTALE D'ERREURS. DES DONNEES SUPPLEMENTAIRES, DE PREFERENCE SURL'UNE DES COMPOSANTES DU BILAN THERMIQUE CONNUE DE FACON SUFFISAMMENT PRECISE, SONT NECESSAIRES POUR PALES MESURES OU POUR IDENTIFIER LES SOURCES D'ERREURS NON ACCEPTABLES.

Détails

  • Titre original : ADVANTAGES AND LIMITATIONS OF THE THORP METHOD OF CROSS-CHECKING WATER CHILLER PERFORMANCE.
  • Identifiant de la fiche : 1991-2262
  • Langues : Anglais
  • Date d'édition : 23/04/1990
  • Source : Source : ASHRAE-FRIGAIR '90, Pretoria
    vol. 2; pap. M.14; 16 p.; 3 tabl.; 12 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.