Calcul de la performance d'une pompe à chaleur à absorption à simple effet utilisant le LiBr + LiNO3 + H2O comme fluide actif.

Performance calculation of single effect absorption heat pump using LiBr + LiNO3 + H2O as working fluid.

Auteurs : JIAN S., LIN F., SHIGANG Z.

Type d'article : Article

Résumé

In order to check the theoretical performance of the new working fluid LiBr + LiNO3 + H2O (mole ratio of LiBr and LiNO3 = 4:1), the theoretical coefficients of performance (COP) of this working fluid and LiBr + H2O were calculated at various operating conditions. The improvement of crystallization problem was also checked. This proposed working fluid was proved to increase the COP by about 5% than LiBr + H2O. The cooling water through absorber and evaporator was heated to higher temperature by this new working fluid. LiBr + LiNO3 + H2O was found to be an alternative to the conventional LiBr + H2O with higher COP and less corrosivity. [Reprinted with permission from Elsevier. Copyright, 2010].

Détails

  • Titre original : Performance calculation of single effect absorption heat pump using LiBr + LiNO3 + H2O as working fluid.
  • Identifiant de la fiche : 30003343
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 30 - n. 17-18
  • Date d'édition : 12/2010
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2010.07.018

Liens


Voir d'autres articles du même numéro (3)
Voir la source