Document IIF

Changement de composition dans les systèmes frigorifiques à recirculation de liquide : étude expérimentale du frigorigène pur R134a et d'un mélange de R32/R134a.

Composition shift in liquid-recirculation refrigerating systems: an experimental investigation for the pure fluid R134a and the mixture R32/R134a.

Auteurs : GIULIANI G., HEWITT N. J., MARCHESI DONATI F., POLONARA F.

Type d'article : Article, Article de la RIF

Résumé

The ability of zeotropic mixtures with a remarkable temperature glide to operate in liquid-recirculation systems is investigated and the results of an experimental comparison between the performances of the pure fluid R134a and the zeotropic mixture R32/R134a (25/75% by mass) are presented. R134a performs slightly better in the liquid-recirculation mode than in the traditional dry-expansion mode; on the other hand, liquid-recirculation configuration has a detrimental effect on the zeotropic mixture's performance. The reason for this detrimental effect is the mixture component separation which occurs at the liquid/vapour separator. The effect of this separation is investigated using gas chromatograph analysis.

Documents disponibles

Format PDF

Pages : 486-498

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Composition shift in liquid-recirculation refrigerating systems: an experimental investigation for the pure fluid R134a and the mixture R32/R134a.
  • Identifiant de la fiche : 2000-0073
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 22 - n. 6