Document IIF
Charge en frigorigène, chute de pression et transfert de chaleur lors de la condensation à l'intérieur de tubes plat.
Refrigerant charge, pressure drop, and condensation heat transfer in flattened tubes.
Auteurs : WILSON M. J., NEWELL T. A., CHATO J. C., et al.
Type d'article : Article, Article de la RIF
Résumé
Horizontal smooth and microfinned copper tubes with an approximate diameter of 9 mm were successively flattened in order to determine changes in flow field characteristics as a round tube is altered into a flattened tube profile. Refrigerants R134a and R410A were investigated over a mass flux range from 75 to 400 kg m-2 s-1 and a quality range from approximately 10-80%. For a given refrigerant mass flow rate, the results show that a significant reduction in refrigerant charge is possible. Pressure drop results show increases of pressure drop at a given mass flux and quality as a tube profile is flattened. Heat transfer results indicate enhancement of the condensation heat transfer coefficient as a tube is flattened. Flattened tubes with an 18° helix angle displayed the highest heat transfer coefficients. Smooth tubes and axial microfin tubes displayed similar levels of heat transfer enhancement. Heat transfer enhancement is dependent on the mass flux, quality and tube profile.
Documents disponibles
Format PDF
Pages : 442-451
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Refrigerant charge, pressure drop, and condensation heat transfer in flattened tubes.
- Identifiant de la fiche : 2003-1695
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 4
- Date d'édition : 06/2003
Liens
Voir d'autres articles du même numéro (12)
Voir la source
Indexation
-
Estimation de la charge en frigorigène dans les...
- Auteurs : MACCHI H., VRINAT G., LEDUCQ D.
- Date : 07/2000
- Langues : Français
- Source : Rev. gén. Froid - vol. 90 - n. 1005
Voir la fiche
-
REMPLISSAGE ET EVACUATION DU FRIGORIGENE DES SY...
- Auteurs : CHRISTENSEN H.
- Date : 1981
- Langues : Allemand
- Source : Klima Kälte Heiz. - vol. 9 - n. 9
Voir la fiche
-
Troubleshooting an undercharge of refrigerant.
- Auteurs : TOMCZYK J.
- Date : 06/05/2002
- Langues : Anglais
- Source : Air Cond. Heat. Refrig. News/achrnews.com - 6 p.
Voir la fiche
-
Boiling and condensation heat transfer for new ...
- Auteurs : MORI H., YOSHIDA S., OHISHI K.
- Date : 2003
- Langues : Anglais
- Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 20 - n. 3
Voir la fiche
-
Using the superheat method to charge air-condit...
- Auteurs : LEONARD H.
- Date : 13/08/2001
- Langues : Anglais
- Source : Air Cond. Heat. Refrig. News/achrnews.com - 9 p.; fig.
Voir la fiche