Document IIF

Chauffage combiné par plancher rayonnant et air forcé avec pompe à chaleur géothermique à détente directe dans une serre nordique.

Combined radiant floor and forced air heating with direct expansion GSHP in a northern greenhouse.

Auteurs : MINEA V.

Résumé

The paper presents the performance of a combined radiant floor and forced-air heating system with a direct-expansion ground-source heat pump (DX-GSHP), developed for, and tested in a conventional (northern climate) greenhouse. The prototype includes a heat pump with three 5-ton scroll compressors, desuperheating and electric back-up coils, a horizontal ground-source heat exchanger buried to a depth of 90 cm (3 ft), and a radiant heating floor. The control strategy developed allowed for the variation in thermal capacity according to the actual heating demand, and thus the obtaining of appropriate operating parameters. The expectation was to reduce by up to 30% the annual heating energy costs compared with a baseline greenhouse, and to provide normal indoor conditions for efficient agricultural production.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Combined radiant floor and forced air heating with direct expansion GSHP in a northern greenhouse.
  • Identifiant de la fiche : 2004-0400
  • Langues : Anglais
  • Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
  • Date d'édition : 17/08/2003

Liens


Voir d'autres communications du même compte rendu (398)
Voir le compte rendu de la conférence