Chute de pression diphasique dans les coudes de retour : résultats expérimentaux obtenus avec le R410A.

Two-phase pressure drop in return bends: experimental results for R410A.

Auteurs : PADILLA M., REVELLIN R., HABERSCHILL P., et al.

Type d'article : Article, Article de la RIF

Résumé

This study presents 238 pressure drop data points measured for two-phase flow of R410A in horizontal return bends. The tube diameter (D) varies from 7.90 to 10.85 mm and the curvature ratio (2R/D) from 3.68 to 4.05. The mass velocity ranges from 179 to 1695 kg/m2.s and the saturation temperatures from 4.6 to 20.7°C. Preliminary tests show that the recovery length necessary for a correct pressure drop measurement downstream of the return bend is less than 20D, for the experimental conditions covered in this study. The singular pressure drop is determined by subtracting the regular pressure drop in straight tube from the total pressure drop. The experimental data are compared against four available correlations found in the literature. The present experimental database for the return bend pressure drop is presented in the Appendix A.

Documents disponibles

Format PDF

Pages : 1854-1865

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Two-phase pressure drop in return bends: experimental results for R410A.
  • Identifiant de la fiche : 30002278
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 34 - n. 8
  • Date d'édition : 12/2011

Liens


Voir d'autres articles du même numéro (40)
Voir la source