Chute de pression diphasique et taux de vide dans des microcanaux : prévision grâce à une analyse de la distribution du régime d'écoulement fondée sur la probabilité.

Prediction of two-phase pressure drop and void fraction in microchannels using probabilistic flow regime mapping.

Auteurs : JASSIM E. W., NEWELL T. A.

Type d'article : Article

Résumé

Probabilistic two-phase flow map pressure drop and void fraction models are developed for 6-port microchannels in order to providea more accurate and common means of predicting void fraction and pressure drop. The models are developed for R134a, R410A, and air-water in 6-port microchannels at 10°C saturation temperatures, qualities from 0 to 1, and mass fluxes varying from 50 to 300 kg/m2.s. The probabilistic flow map models developed are found to accurately predict void fraction and pressure drop for the entire quality range and for all three fluids. [Reprinted with permission from Elsevier. Copyright, 2006].

Détails

  • Titre original : Prediction of two-phase pressure drop and void fraction in microchannels using probabilistic flow regime mapping.
  • Identifiant de la fiche : 2006-2847
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 49 - n. 15-16
  • Date d'édition : 07/2006

Liens


Voir d'autres articles du même numéro (6)
Voir la source