COEFFICIENT DE TRANSFERT DE CHALEUR. EBULLITION DE L'ECOULEMENT DIPHASIQUE DU R134A.

HEAT TRANSFER COEFFICIENT. TWO-PHASE FLOW BOILING OF HFC134A.

Auteurs : HAMBRAEUS K.

Résumé

ON ETUDIE L'EVAPORATION DU R134A A L'INTERIEUR DE TUBES LISSES ET HORIZONTAUX, AVEC DU FRIGORIGENE PUR ET DES MELANGES HUILE-FRIGORIGENE. LE FLUX THERMIQUE A VARIE ENTRE 2 ET 10 KILOWATTS/M2. LA TENEUR EN HUILE VARIE D'UN POURCENTAGE EN MASSE DE 0 A 2,5 (HUILE SYNTHETIQUE EXP-0275). ON OBSERVE QUE LE R134A EXEMPT D'HUILE PRESENTE UN COEFFICIENT DE TRANSFERT DE CHALEUR SUPERIEUR A CELUI DU R22. A 2 ET 4 KILOWATTS/M2, LE COEFFICIENT DE TRANSFERT DE CHALEUR A UNE VALEUR MAXIMALE POUR UNE TENEUR EN HUILE D'UN POURCENTAGE EN MASSE D'ENVIRON 0,5. ON NE NOTE AUCUNE AUGMENTATION POUR 6 KILOWATTS/M2. ON COMPARE EGALEMENT LES COEFFICIENTS DE TRANSFERT DE CHALEUR RELATIFS AU FRIGORIGENE PUR A DES CORRELATIONS EXISTANTES. LA CORRELATION DE PIERRE PREVOIT DES VALEURS AVEC UNE PRECISION SATISFAISANTE. LA RELATION DE CHEN MODIFIEE PAR JUNG SURESTIME LE COEFFICIENT DE TRANSFERT DE CHALEUR.

Détails

  • Titre original : HEAT TRANSFER COEFFICIENT. TWO-PHASE FLOW BOILING OF HFC134A.
  • Identifiant de la fiche : 1991-1064
  • Langues : Anglais
  • Date d'édition : 17/07/1990
  • Source : Source : USNC-IIR/Proc. 1990 Refrig. Conf., Purdue Univ./ASHRAE, Purdue CFC Conf./Purdue Univ., Ray W. Herrick Lab., Sch. mech. Eng.
    205-214; 10 fig.; 8 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.