Document IIF

Coefficient de transfert de chaleur par évaporation et chute de pression du R-446A, du R1234ze(E) et du R-1233ZD(E).

Evaporation heat transfer coefficient and pressure drop of R-446A, R1234ze(E), and r-1233ZD(E).

Numéro : pap. TP-0131

Auteurs : KIM M., CHO K.

Résumé

The present study investigated evaporation heat transfer coefficient and pressure drop of R-446A, R-1234ze(E), and R-1233zd(E) as low GWP refrigerant. Test apparatus consisted of a test section with horizontal stainless tube, a pump, a constant temperature bath, a pre-heater, a condenser, a DC power supply etc. Test parameters were quality from 0 to 1, mass flux from 100 to 400kg/m2s, heat flux from 10 to 30kW/m2, saturation temperatures from 5 to 10°C, and tube diameters of 5, 7.4, and 9mm. The heat transfer coefficients of R-446A, R-1234ze(E), R-1233zd(E) were increased as the mass flux, heat flux and saturation temperature was increased, while they were decreased as the tube diameter was increased. The pressure drops were increased as the mass flux and heat flux was increased, while they were decreased as the saturation temperature and tube diameter were increased. Pressure drops of R-1233zd(E) showed the largest among three low GWP refrigerants.

Documents disponibles

Format PDF

Pages : 6

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Evaporation heat transfer coefficient and pressure drop of R-446A, R1234ze(E), and r-1233ZD(E).
  • Identifiant de la fiche : 30021587
  • Langues : Anglais
  • Source : 5th IIR Conference on Thermophysical Properties and Transfer Processes of Refrigerants.
  • Date d'édition : 23/04/2017
  • DOI : http://dx.doi.org/10.18462/iir.tptpr.2017.0131

Liens


Voir d'autres communications du même compte rendu (84)
Voir le compte rendu de la conférence