Comparaison des performances de régulation des régulateurs PID et des régulateurs d'humidité pour la régulation du chauffage, de la ventilation et du conditionnement d'air.
Comparison in control performance between PID and humidity controllers for HVAC control.
Auteurs : NODA Y., YAMAZAKI T., MATSUBA T., et al.
Résumé
This paper concerns a new design method for robust controllers that achieve robust stability as well as adequate disturbance suppression characteristics. Of particular interest to the authors is how to design the controller for HVAC systems with unknown dynamics and imprecisely known parameters. In a previous paper, a robust proportional-plus-integral-plus derivative (PID) controller was designed for temperature control of a single-zone room that was commonly approximated by a first-order lag plus deadtime system. The PID gains obtained by solving a two-disk type mixed sensitivity problem have been modified to contrast to those tuned by the traditional Ziegler-Nichols rule. The previous results showed that the proposed PID controller was effective enough for practical applications. In the paper, the robust controller is redesigned for the same plant with changes in characteristics of the plant through humidity control theory. A practical and systematic design method for the controller is proposed. The paper demonstrates the practical applicability of the controller for a typical plant in HVAC industries. To evaluate the control performance, a comparison is made between humidity control and PID control. Numerical simulations suggest that the humidity controller enables an improvement in disturbance suppression characteristics to some extent, but it does not offer substantial advantages for the HVAC systems.
Détails
- Titre original : Comparison in control performance between PID and humidity controllers for HVAC control.
- Identifiant de la fiche : 2005-1401
- Langues : Anglais
- Source : ASHRAE Transactions. 2003 Winter Meeting, Chicago, Illinois. Volume 109, part 1 + CD-ROM.
- Date d'édition : 2003
Liens
Voir d'autres communications du même compte rendu (32)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Autres équipements de conditionnement d'air
- Mots-clés : Conception; Régulation; Performance; Modélisation; Conditionnement d'air
-
What's up with cooling towers?
- Auteurs : MORRISON F. T.
- Date : 07/2004
- Langues : Anglais
- Source : ASHRAE Journal - vol. 46 - n. 7
Voir la fiche
-
Echangeurs de chaleur pour conditionneurs d'air.
- Auteurs : SHIKAZONO N.
- Date : 09/2000
- Langues : Japonais
- Source : Refrigeration - vol. 75 - n. 875
Voir la fiche
-
Design, construction and performance analysis o...
- Auteurs : KOYUNCU T., EKER B., PINAR Y.
- Date : 15/09/2001
- Langues : Anglais
- Source : CLIMA 2000. 7th REHVA World Congress, Naples 2001 [CD-ROM + Hard-copy abstracts].
Voir la fiche
-
Variable air volume system heat recovery econom...
- Auteurs : SCOFIELD C. M., DESCHAMPS N., WEAVER T. S.
- Date : 05/2016
- Langues : Anglais
- Source : ASHRAE Journal - vol. 58 - n. 5
Voir la fiche
-
Dynamic modelling of the storage of an encapsul...
- Auteurs : KOUSKSOU T., BEDECARRATS J. P., DUMAS J. P., et al.
- Date : 07/2005
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 25 - n. 10
Voir la fiche