Steady and transient behaviour of LiBr absorption chillers of low capacity.

Auteurs : LAZZARIN R.

Type d'article : Article, Article de la RIF

Résumé

Two, low capacity, LiBr, absorption chillers (4.5 and 25 kW) expressly designed for solar cooling have been tested. The manufacturer's performance curves have been checked, then the investigation was extended to different values of the main parameters. Transient behaviour has been examined. For solar cooling duties it was found that control by simple on-off cycling is unacceptable owing to the large resulting energy loss. Two alternative control strategies are suggested together with the appropriate plant schemes.