Concentrations fongiques sur les surfaces intérieures des conduits de ventilation : isolation par mousse à alvéoles hermétiques comparée à l'isolation par du verre fibreux et par du métal galvanisé.
Fungal levels on interior surfaces of ventilation ductwork: closed cell foam insulation versus fibrous glass insulation and galvanized metal.
Auteurs : ELLRINGER P. J., HENDRICKSON S. C., YANG C. S., et al.
Résumé
The study compares the fungal populations present on the airstream surfaces of fibrous glass insulation, bare galvanized metal, and closed cell foam insulation, which were all subjected to the same environmental conditions over a five-year period. It shows that fibrous glass liners have fungal levels thousands of times higher than galvanized metal or closed cell foam insulation when exposed to the same environmental conditions. The porous fibrous glass insulation with its rough surface is more likely to hold onto organic debris from the airstream than bare galvanized metal or closed cell foam insulation. Fungi in high moisture areas can feed on this collected organic debris. Porous fibrous glass insulation in contact with the airstream surface can become a reservoir of fungal organisms, which can be a source of elevated levels of fungal organisms in the occupied space. Elevated levels of fungal organisms can degrade the air quality for building occupants. Galvanized metal and closed cell foam insulation have smooth surfaces, which are less likely to collect debris and encourage fungal growth. Galvanized metal and closed cell foam insulation are better choices for interior ductwork surfaces than fibrous glass insulation, especially in high moisture areas such as near cooling coils and humidifiers.
Détails
- Titre original : Fungal levels on interior surfaces of ventilation ductwork: closed cell foam insulation versus fibrous glass insulation and galvanized metal.
- Identifiant de la fiche : 2005-1468
- Langues : Anglais
- Source : IAQ 2001. Moisture, microbes and health effects: indoor air quality and moisture in buildings [CD-ROM].
- Date d'édition : 2002
Liens
Voir d'autres communications du même compte rendu (9)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Conditionnement d'air : généralités;
Conditionnement d'air pour le confort - Mots-clés : Spore; Immeuble; Moisissure; Métal; Verre; Ventilation; Santé; Mousse; Matériau; Gaine; Isolation; Conditionnement d'air
-
Fungal spores dispersed from fiberglass ductboa...
- Auteurs : BUTTNER M. P., STETZENBACH L. D.
- Date : 2002
- Langues : Anglais
- Source : IAQ 2001. Moisture, microbes and health effects: indoor air quality and moisture in buildings [CD-ROM].
Voir la fiche
-
Fungal colonisation of porous air handling comp...
- Auteurs : PRICE D. L., RAMEY D. L., ABBLITT L. L.
- Date : 01/05/1995
- Langues : Anglais
- Source : 1995 AIRAH Conference Proceedings.
Voir la fiche
-
SYNTHETIC MINERAL FIBRES IN HVAC SYSTEMS: IS TH...
- Auteurs : TAYLOR G.
- Date : 1989
- Langues : Anglais
- Source : AIRAH J. - vol. 43 - n. 9
Voir la fiche
-
Healthy buildings.
- Auteurs : WYON D., BUNN R., APPLEBY P., PERERA E., PARKINS L.
- Date : 06/1992
- Langues : Anglais
- Source : J. chart. Inst. Build. Serv. - vol. 14 - n. 6
Voir la fiche
-
The fundamentals of fungi.
- Auteurs : ARMSTRONG S.
- Date : 11/2002
- Langues : Anglais
- Source : ASHRAE Journal - vol. 44 - n. 11
Voir la fiche