CONCEPTION OPTIMALE D'UN SYSTEME FRIGORIFIQUE ET DE POMPE A CHALEUR EN CASCADE MULTIETAGE.

OPTIMUM DESIGN OF MULTISTAGE CASCADED REFRIGERATION-HEAT PUMP SYSTEM.

Auteurs : GUPTA V. K.

Type d'article : Article

Résumé

UN SYSTEME FRIGORIFIQUE ET DE POMPE ACHALEUR EN CASCADE MULTI-ETAGE EMPLOYANT LA COMPRESSION BIETAGEE DU COTE HAUTE TEMPERATURE ET LA COMPRESSION MONO-ETAGEE DU COTE BASSE TEMPERATURE EST OPTIMISE NUMERIQUEMENT. ON PRESENTE LES QUANTITES PREVUES CORRESPONDANT A LA PERFORMANCE OPTIMALE ET AU COUT D'EXPLOITATION MINIMAL DU SYSTEME (TEMPERATURES ENTRE LES ETAGES ET DE CONDENSATION, DEBITS D'EAU ECONOMIQUES, BESOINS D'ENERGIE). LE R22, FRIGORIGENE LE PLUS COURANT ET RELATIVEMENT BON MARCHE EST CHOISI POUR LESOUS-SYSTEME DE LA POMPE A CHALEUR ET LE R13 POUR LE SOUS-SYSTEME FRIGORIFIQUE. LES TEMPERATURES DE L'EVAPORATEUR ET AMBIANTES VARIENT RESPECTIVEMENT DE 213 A 243 K (-60 A -30 DEG C) ET DE 283 A 333 K (10 A 60 DEG C). LE COP GLOBAL DU SYSTEME EST DE 2,8 A 7,4 SI LE SYSTEME FONCTIONNE DANS LES DOMAINES CONSIDERES DES PARAMETRES DE FONCTIONNEMENT.

Détails

  • Titre original : OPTIMUM DESIGN OF MULTISTAGE CASCADED REFRIGERATION-HEAT PUMP SYSTEM.
  • Identifiant de la fiche : 1987-1968
  • Langues : Anglais
  • Source : J. Heat Recov. Syst. - vol. 6 - n. 3
  • Date d'édition : 1986