Confort thermique, uniformité et efficacité de la ventilation dans les chambres des patients : évaluation de la performance à l'aide d'indices de ventilation.

Thermal comfort, uniformity, and ventilation effectiveness in patient rooms: performance assessment using ventilation indices.

Résumé

The paper describes a study of the performance of a ventilation system in a typical patient room using CFD modelling and calculations of various ventilation indices. The results show that the use of baseboard heating is necessary in extreme weather conditions. In particular, good occupant conditions are virtually impossible to achieve without baseboard heating. Further, in general weather conditions, a ventilation rate of 4 ACH provides adequate conditions, though an increase to 5 or 6 ACH is optimum.

Détails

  • Titre original : Thermal comfort, uniformity, and ventilation effectiveness in patient rooms: performance assessment using ventilation indices.
  • Identifiant de la fiche : 2001-2463
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2000 ASHRAE Annual Meeting, Minneapolis, Minnesota + CD-ROM.
  • Date d'édition : 24/06/2000
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (49)
Voir le compte rendu de la conférence