Document IIF

Corrélation généralisée de la chute de pression lors de l'évaporation et de la condensation dans des tubes lisses à micro-ailettes.

Generalized pressure drop correlation for evaporation and condensation in smooth and micro-fin tubes.

Résumé

NIST micro-fin tube pressure drop data for R134a, R22, R125, R32, R407C, R410A and R32/R134a (25/27% mass) were regressed to a modified Pierre correlation. The NIST database was post-predicted with an average absolute residual of 10.8%. Further validations performed with extensive data from the literature on lubricant-free refrigerants showed that the average absolute residual between measurements and predictions did not exceed 17.6%. The condensation and evaporation pressure drops for different refrigerant/lubricant mixtures were predicted with average absolute residuals not exceeding 19.6% and 25.0%, respectively.

Documents disponibles

Format PDF

Pages : 2001-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Generalized pressure drop correlation for evaporation and condensation in smooth and micro-fin tubes.
  • Identifiant de la fiche : 2003-0609
  • Langues : Anglais
  • Source : Thermophysical Properties and Transfer Processes of New Refrigerants.
  • Date d'édition : 03/10/2001

Liens


Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence