Critères de variation et de conception du rapport de charge thermique d'un générateur pour un refroidisseur à à absorption double effet air-bromure de lithium refroidi par air.
Variation and design criterion of heat load ratio of generator for air cooled lithium bromide-water double effect absorption chiller.
Résumé
The heat load ratio of generator (HLRG) is a special system parameter because it is not fixed at the design value but changes with the working condition. For the air cooled chiller, the deviation from the design working condition occurs easily due to the variation of the surrounding temperature. The system is likely to suffer from crystallization when the working condition is different from the designed one if the HLRG is designed improperly. Consequently, the design criterion of HLRG based on a broad range of working condition is essential and urgent to the development of air cooled lithium bromide–water double effect absorption chiller. This paper mainly deals with the variation of HLRG with the working condition as well as corresponding design criterion. Four types of double effect chillers named series, pre-parallel, rear parallel and reverse parallel flow system were considered. The parametric model was developed by the introduction of a new thermodynamic relationship of generator. The change of HLRG for different types of chillers with the working condition was analyzed and compared. The corresponding design criterion of HLRG was presented. This paper is helpful for further improvement of the performance and reliability of air cooled lithium bromide–water double effect absorption chiller.
Détails
- Titre original : Variation and design criterion of heat load ratio of generator for air cooled lithium bromide-water double effect absorption chiller.
- Identifiant de la fiche : 30016750
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 96
- Date d'édition : 05/03/2016
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2015.11.099
Liens
Voir d'autres articles du même numéro (32)
Voir la source
Indexation
-
Low pressure showered evaporator in absorption ...
- Auteurs : CURKA D., MOLOTTA M.
- Date : 02/09/2009
- Langues : Anglais
- Source : Compressors 2009: 7th International Conference on Compressors and Coolants
- Formats : PDF
Voir la fiche
-
Production de froid à partir de chaleur basse t...
- Auteurs : LARGER D.
- Date : 03/1997
- Langues : Français
- Source : Rev. gén. Froid - vol. 87 - n. 971
Voir la fiche
-
The experimental investigation on the plastic h...
- Auteurs : ZHANG X. B., HU Y. C., YU Z. T., et al.
- Date : 05/04/2008
- Langues : Anglais
- Source : Cryogenics and refrigeration. Proceedings of ICCR'2008.
Voir la fiche
-
Development of a packed bed regenerative soluti...
- Auteurs : PAURINE A., MAIDMENT G. G., EAMES I. W.
- Date : 10/2013
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 60 - n. 1-2
Voir la fiche
-
Direct-heat exchange water evaporator for vapou...
- Auteurs : EAMES I. W., WU S., SABIR H.
- Date : 02/06/1998
- Langues : Anglais
- Source : Natural Refrigerants, Energy Efficiency, Cost and Safety. Natural Working Fluids '98. IIR-Gustav Lorentzen Conference.
- Formats : PDF
Voir la fiche