Développement d'un transformateur de puissance de classe 500 kVA en supraconducteur à base d'oxyde fonctionnant à la température de l'azote liquide.

Development of a 500 kVA-class oxide-superconducting power transformer operated a liquid-nitrogen temperature.

Auteurs : FUNAKI K., IWAKUMA M., KAJIKAWA K., et al.

Type d'article : Article

Résumé

The authors have designed and constructed a 500 kVA-class oxide-superconducting power transformer. The windings are cooled by liquid nitrogen or subcooled nitrogen in a G-FRP cryostat of 785 millimeters in diameter and 1210 millimeters in height, that has a room-temperature space for an iron core with the diameter of 314 millimeters. The primary and secondary windings are three-stand and six-strand parallel conductors of a bismuth-2223 multi-filamentary tape with silver sheath, respectively. The strand 0.22 millimeter thick and 3.5 millimeter wide has 61 filaments with no twisting.

Détails

  • Titre original : Development of a 500 kVA-class oxide-superconducting power transformer operated a liquid-nitrogen temperature.
  • Identifiant de la fiche : 1999-2088
  • Langues : Anglais
  • Source : Cryogenics - vol. 38 - n. 2
  • Date d'édition : 02/1998

Liens


Voir d'autres articles du même numéro (7)
Voir la source