Développement d’une nouvelle méthodologie d’essai en laboratoire pour le vieillissement rapide des filtres de CVC.
Development of a new laboratory test methodology for rapid ageing of HVAC filters.
Numéro : 3228
Auteurs : HUANG C., CHUANG T-K., GOMES I., AJALA L., CRAM E. P., JUNG N., BOOR B. E.
Résumé
Air filters installed in residential and commercial HVAC systems encounter a complex mixture of aerosols of outdoor and indoor origin during their service life. Standardized laboratory test methodologies are important for evaluating the loading behavior of HVAC filters. Loading aerosols commonly used to age HVAC filters include various test dusts (ISO-12103-1-A2, ISO-12103-1-A4, ASHRAE Test Dust) that are primarily composed of coarse mode particles (1 to 100 μm). However, urban aerosol mass size distributions often feature a prominent accumulation mode between 0.1 and 1 μm that is not well represented by traditional loading aerosols. The aim of this study is to develop a new laboratory test methodology for rapid ageing of HVAC filters with a representative urban aerosol mass size distribution at a high concentration to better predict long-term changes in HVAC filter performance. A HVAC filter test rig was custom designed and built following ASHRAE 52.2 specifications to artificially age HVAC filters with sub-micron potassium chloride (KCl) aerosol produced by a thermal aerosol generator. The KCl aerosol is formed by burning KCl sticks in a high temperature oxygen-propane flame and is delivered to the test rig via a damper-controlled intake duct. The results demonstrate that the new sub-micron KCl loading aerosol is a time- and cost-effective technique to artificially age HVAC filters with a particle mass size distribution representative of that found in HVAC installations in buildings.
Documents disponibles
Format PDF
Pages : 10 p.
Disponible
Gratuit
Détails
- Titre original : Development of a new laboratory test methodology for rapid ageing of HVAC filters.
- Identifiant de la fiche : 30032949
- Langues : Anglais
- Source : 2024 Purdue Conferences. 8th International High Performance Buildings Conference at Purdue.
- Date d'édition : 15/07/2024
Liens
Voir d'autres communications du même compte rendu (63)
Voir le compte rendu de la conférence
Indexation
- Thèmes : Qualité de l'air intérieur
- Mots-clés : Filtre; Qualité de l'air; Immeuble
-
Better filtration for healthier buildings.
- Auteurs : WHEELER A. E.
- Date : 06/1994
- Langues : Anglais
- Source : ASHRAE Journal - vol. 36 - n. 6
Voir la fiche
-
Filter selection for air quality purposes.
- Auteurs : RABER R. R., FENCL F. B.
- Date : 07/1993
- Langues : Anglais
- Source : AIRAH J. - vol. 47 - n. 7
Voir la fiche
-
Tools for the analysis of gas-phase air-cleanin...
- Auteurs : AXLEY J. W.
- Date : 1994
- Langues : Anglais
- Source : ASHRAE Transactions 1994.
Voir la fiche
-
Des concepts pour combattre le syndrome des imm...
- Auteurs : KOCH P.
- Date : 03/1994
- Langues : Allemand
- Source : KI Luft Kältetech. - vol. 30 - n. 3
Voir la fiche
-
Current considerations in the development of ve...
- Auteurs : BLUYSSEN P. M.
- Date : 05/1993
- Langues : Anglais
- Source : Indoor Environ. - vol. 2 - n. 3
Voir la fiche