Développement et résultats en terme de performance transitoire d'un système de refroidissement monoétagé à adsorption au HFC-134a-charbon actif, en cycle fermé.

Development and transient performance results of a single stage activated carbon-HFC-134a closed cycle adsorption cooling system.

Auteurs : BANKER N. D., PRASAD M., DUTTA P., et al.

Type d'article : Article

Résumé

A laboratory model of a thermally driven adsorption refrigeration system with activated carbon as the adsorbent and 1,1,1,2-tetrafluoroethane (HFC-134a) as the refrigerant was developed. The single stage compression system has an ensemble of four adsorbers packed with Maxsorb II specimen of activated carbon that provide a near continuous flow which caters to a cooling load of up to 5 W in the 5-18°C region. The objective was to utilise the low grade thermal energy to drive a refrigeration system that can be used to cool some critical electronic components. The laboratory model was tested for its performance at various cooling loads with the heat source temperature from 73 to 93°C. The pressure transients during heating and cooling phases were traced. The cyclic steady state and transient performance data are presented. [Reprinted with permission from Elsevier. Copyright, 2010].

Détails

  • Titre original : Development and transient performance results of a single stage activated carbon-HFC-134a closed cycle adsorption cooling system.
  • Identifiant de la fiche : 30001444
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 30 - n. 10
  • Date d'édition : 07/2010
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2010.01.027