Document IIF
Diagnostic thermoéconomique innovant de défaillances multiples dans des conditionneurs d'air : améliorations méthodologiques et fiabilité accrue des résultats.
Innovative thermoeconomic diagnosis of multiple faults in air conditioning units: methodological improvements and increased reliability of results.
Auteurs : PIACENTINO A., TALAMO M.
Type d'article : Article, Article de la RIF
Résumé
Thermoeconomic faults diagnosis of air conditioning units is a pioneeristic approach to detect single or multiple faults and quantify their impact in terms of additional energy consumption. The poor reliability of conventional thermoeconomic approaches has been limiting the interest for practical applications of this technique. In this paper an improved thermoeconomic diagnosis is proposed and applied to a reference 120 kWc air-cooled air conditioning system; a simulator is used to evaluate thermodynamic data under normal and faulty conditions. Four faults are individually or simultaneously imposed: fouling at condenser and evaporator, refrigerant undercharge and compressor valve leakage. For setting up the diagnostic tool only a few numerical or experimental tests are required; the results testify the procedure to be sufficiently reliable both when heavy or light faults are considered. Also, the performance of the diagnostic procedure slightly improves when the effects of “system level” faults like refrigerant undercharge are preliminarily filtered.
Documents disponibles
Format PDF
Pages : 2343-2365
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Innovative thermoeconomic diagnosis of multiple faults in air conditioning units: methodological improvements and increased reliability of results.
- Identifiant de la fiche : 30009850
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 36 - n. 8
- Date d'édition : 12/2013
Liens
Voir d'autres articles du même numéro (37)
Voir la source
-
Development and evaluation of a simple model-ba...
- Auteurs : REDDY T. A.
- Date : 23/06/2007
- Langues : Anglais
- Source : ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
Voir la fiche
-
Automated proactive fault isolation: a key to a...
- Auteurs : KATIPAMULA BRAMBLEY M.
- Date : 23/06/2007
- Langues : Anglais
- Source : ASHRAE Transactions. 2007 Annual Meeting, Long Beach, CA. Volume 113, part 2 + CD-ROM.
Voir la fiche
-
Evaluating the performance of fault detection a...
- Auteurs : YUILL D. P., BRAUN J. E.
- Date : 10/2013
- Langues : Anglais
- Source : HVAC&R Research - vol. 19 - n. 7
Voir la fiche
-
Evaluating fault detection and diagnostics prot...
- Auteurs : YUILL D., BRAUN J.
- Date : 16/07/2012
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Eskom and air conditioning. 4. Installation sho...
- Auteurs : ALDER G.
- Date : 07/2008
- Langues : Anglais
- Source : RACA Journal - vol. 24 - n. 5
- Formats : PDF
Voir la fiche