Document IIF
Diminution de la performance d'un condenseur multitubulaire lorsqu'on remplace le R22 par des mélanges zéotropiques. 1. Analyse des données expérimentales.
Reasons for drop in shell-and-tube condenser performance when replacing R22 with zeotropic mixtures. 1. Analysis of experimental findings.
Auteurs : SAJJAN D., KARLSSON T., VAMLING L.
Type d'article : Article, Article de la RIF
Résumé
An experimental and theoretical investigation was made to find out the reasons for the drop in shell-and-tube condenser performance when replacing R22 with a zeotropic mixture R407C. Measurements show that at lower condenser loads the reduction in performance can be as large as 70% compared to the full condenser load. Calculation results are compared with experimental results for two different condensers, one with micro-finned tubes and one with 3-D finned tubes. Calculations show that the degree of mixing of the newly formed condensate on a tube and the drained condensate is a factor influential enough to explain the performance drop. 3-D finned tubes seem to have better mixing in the condensate than integral finned tubes.
Documents disponibles
Format PDF
Pages : 552-560
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Reasons for drop in shell-and-tube condenser performance when replacing R22 with zeotropic mixtures. 1. Analysis of experimental findings.
- Identifiant de la fiche : 2004-2791
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 5
- Date d'édition : 08/2004
Liens
Voir d'autres articles du même numéro (11)
Voir la source
Indexation
-
Reasons for drop in shell-and-tube condenser pe...
- Auteurs : KARLSSON T., VAMLING L.
- Date : 08/2004
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 5
- Formats : PDF
Voir la fiche
-
Comparison of flow fields of a pure fluid and a...
- Auteurs : KARLSSON T.
- Date : 02/05/2005
- Langues : Anglais
- Source : 8th IEA Heat Pump Conference 2005: global advances in heat pump technology, applications, and markets. Conference proceedings [CD-ROM].
Voir la fiche
-
ETUDE EXPERIMENTALE SUR UN CONDENSEUR A CALANDR...
- Auteurs : UEHARA H., NAKAOKA T., TAKASUE H.
- Date : 1989
- Langues : Japonais
- Source : Trans. JAR - vol. 6 - n. 3
Voir la fiche
-
Przejmowanie ciepla podszas jednofazowej konwek...
- Auteurs : CIESLINSKI J. T., GRODZ A.
- Date : 06/2011
- Langues : Polonais
- Source : Technika Chlodnicza i Klimatyzacyjna - vol. 18 - n. 6-7
- Formats : PDF
Voir la fiche
-
Condensation heat transfer coefficients for R22...
- Auteurs : APREA C., GRECO A., VANOLI G. P.
- Date : 06/2003
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 4
- Formats : PDF
Voir la fiche