Ebullition d'un mélange d'ammoniac-lubrifiant à l'extérieur d'un tube à surface améliorée dans un évaporateur noyé.

Boiling of ammonia-lubricant mixture on a horizontal enhanced tube in a flooded evaporator with inlet vapour quality.

Auteurs : ZHENG J., CHYU M. C., AYUB Z.

Type d'article : Article, Article de la RIF

Résumé

In a flooded evaporator of an ammonia vapour-compression refrigeration system, boiling commonly takes place with ammonia mixed with compressor lubricant and subjected to a vapour quality at the inlet of the evaporator. In this study, flooded boiling tests of ammonia on an enhanced tube under simultaneous influence of a miscible lubricant and inlet quality were conducted. The results suggest that the boiling heat transfer coefficient increases with both saturation temperature and heat flux. The coefficient slightly increases or does not significantly vary with the inlet quality. The coefficient in general is decreased by adding lubricant to the refrigerant, but the coefficient does not necessarily decrease as the lubricant concentration increases. The lubricant effect is generally more significant than the inlet quality effect. A correlation was developed based on the present data for flooded boiling of lubricant/ammonia mixture on an enhanced horizontal tube under the influence of inlet quality.

Documents disponibles

Format PDF

Pages : 564-572

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Boiling of ammonia-lubricant mixture on a horizontal enhanced tube in a flooded evaporator with inlet vapour quality.
  • Identifiant de la fiche : 2008-1556
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 31 - n. 4
  • Date d'édition : 06/2008