Ecoulement diphasique de frigorigènes de remplacement à travers des orifices de tubes courts : corrélation générale.

A generalized correlation for two-phase flow of alternative refrigerants through short tube orifices.

Auteurs : CHOI J., CHUNG J. T., KIM Y.

Type d'article : Article, Article de la RIF

Résumé

The objective of this study was to develop a generalized correlation for the prediction of refrigerant flow rate through short tube orifices using alternative refrigerants. The generalized correlations for two-phase and subcooled inlet conditions were separately derived from a power law form of dimensionless parameters generated by the Buckingham Pi theorem. The database for the present correlation includes extensive experimental data for R12, R22, R134a, R407C, R410A, and R502 obtained from the literature. For subcooled inlet conditions at the short tube entrance, the correlation yields an average deviation of 0.3% and a standard deviation of 6.1% based on the present database, while for two-phase inlet conditions it predicts the database values with an average deviation of 0.2% and a standard deviation of 5.0%. The relative deviations of the predictions using the present correlations for two-phase and subcooled inlet conditions range from -21% to 18%.

Documents disponibles

Format PDF

Pages : 393-400

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A generalized correlation for two-phase flow of alternative refrigerants through short tube orifices.
  • Identifiant de la fiche : 2004-1574
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 4
  • Date d'édition : 06/2004