Document IIF

Effet de faisceau d'un mélange ammoniac/huile en ébullition sur un faisceau horizontal avec une tuyauterie et un dispositif d'entrée améliorés.

Bundle effect of ammonia/lubricant mixture boiling on a horizontal bundle with enhanced tubing and inlet quality.

Auteurs : CHYU M. C., ZHENG J., AYUB Z.

Type d'article : Article, Article de la RIF

Résumé

Shell-side heat transfer coefficients of individual tubes for ammonia/lubricant mixture boiling on a 3 x 5 enhanced tube bundle were measured, enabling a detailed study of tube bundle effect under the influences of inlet quality, concentration of miscible lubricant (co-polymer of polyalkylene glycol, PAG), saturation temperature, and heat flux. Tests were conducted in the range of heat flux from 3.2 to 32.0 kW/m2, simulated inlet quality from 0.0 to 0.4, saturation temperature from -13.2 to 7.2°C, and lubricant concentration from 0 to 10%. The data show that bundle effect is more significant at a higher saturation temperature. Most of the data in the bottom row are lower than the single-tube heat transfer coefficient data at a low saturation temperature. Lubricant renders the heat transfer coefficient lower in lower rows and higher in higher rows, therefore a larger range of data variation.

Documents disponibles

Format PDF

Pages : pp. 1876-1885

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Bundle effect of ammonia/lubricant mixture boiling on a horizontal bundle with enhanced tubing and inlet quality.
  • Identifiant de la fiche : 2009-2277
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 8
  • Date d'édition : 12/2009

Liens


Voir d'autres articles du même numéro (8)
Voir la source