Effet de l'écoulement réduit de l'air sur l'évaporateur vis à vis de la performance à haute température des conditionneurs d'air.
Effect of reduced evaporator airflow on the high temperature performance of air conditioners.
Auteurs : RODRIGUEZ A. G., O'NEAL D., et al.
Type d'article : Article
Résumé
Reports the testing of two residential-sized air conditioners in psychrometric rooms at reduced evaporator airflows from 0 to 50% below that recommended by the manufacturer of each of the units. Outdoor temperatures ranged from 35 to 49 deg C. Results at 35 deg C indicated that the reduction in air produced a larger drop in capacity and COP for the orifice-controlled unit than for the thermal expansion valve-controlled unit. The power showed less than a 4% reduction for either unit as the air flow was reduced by 50%.
Détails
- Titre original : Effect of reduced evaporator airflow on the high temperature performance of air conditioners.
- Identifiant de la fiche : 1998-3097
- Langues : Anglais
- Source : Energy Build. - vol. 24 - n. 3
- Date d'édition : 10/1996
Liens
Voir d'autres articles du même numéro (6)
Voir la source
Indexation
-
Simulation of recombined household multi-split ...
- Auteurs : LI Z., WANG B., LI X., et al.
- Date : 05/05/2017
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 117
Voir la fiche
-
Monozone modelisation of natural ventilation wi...
- Auteurs : BERNARD A. M., VIALLE P. J., LEMAIRE M. C., et al.
- Date : 11/09/2001
- Langues : Anglais
Voir la fiche
-
RESIDENTIAL AIR CONDITIONING ENERGY CALCULATIONS.
- Auteurs : KHATTAR M. K.
- Date : 1984
- Langues : Anglais
Voir la fiche
-
Analysis on the performance degradation for res...
- Auteurs : ZHENG B., LIANG X.
- Date : 12/07/2010
- Langues : Anglais
- Formats : PDF
Voir la fiche
-
Guide pratique de l'ADEME : le confort d'été.
- Date : 2003
- Langues : Français
- Source : Ademe, Guide prat. - 13 p.; fig.; phot.
Voir la fiche