Effet de l'inclinaison sur la performance côté air d'un échangeur de chaleur en aluminium brasé dans des conditions sèches et humides.

Effect of inclination on the airside performance of a brazed aluminum heat exchanger under dry and wet conditions.

Auteurs : KIM M. H., YOUN B., BULLARD C. W.

Type d'article : Article

Résumé

The study presents the effect of an inclination angle from the vertical position on the airside thermal hydraulic performance for a multi-louvered fin and flat tube heat exchanger. For a heat exchanger with a louver angle of 27 °C, fin pitch of 1.4 mm and flow depth of 20 mm, a series of tests for dry and wet surface conditions were conducted for the airside Reynolds numbers of 100-300. The heat transfer coefficients and the pressure drops for the wet conditions revealed the importance of the role of condensate drainage.

Détails

  • Titre original : Effect of inclination on the airside performance of a brazed aluminum heat exchanger under dry and wet conditions.
  • Identifiant de la fiche : 2002-1792
  • Langues : Anglais
  • Source : International Journal of Heat and Mass Transfer - vol. 44 - n. 24
  • Date d'édition : 12/2001