Effet de la charge en frigorigène sur la performance des systèmes de conditionnement d'air.

Effect of refrigerant charge on the performance of air conditioning systems.

Auteurs : GOSWAMI D. Y., LEUNG M., et al.

Type d'article : Article

Résumé

The authors describe an experimental investigation of the effect of low charge level of R22 on the performance of a 3-ton residential air conditioning system. The results are presented and discussed. They show that if a system is undercharged to 90% then the effect is small - a 3.5% reduction in cooling capacity and a 2% decrease in the COP. However, the system performance suffers serious deterioration if the level of charge drops below 80%. Economic analysis showed that the cost of properly charging an undercharged system at 85% charge level, can pay for itself in savings in 3-4 months.

Détails

  • Titre original : Effect of refrigerant charge on the performance of air conditioning systems.
  • Identifiant de la fiche : 2002-2602
  • Langues : Anglais
  • Source : Int. J. Energy Res. - vol. 25 - n. 8
  • Date d'édition : 25/06/2001