Document IIF

Effet de la purge par air neuf sur l'efficacité de la récupération d'énergie à partir de l'air extrait, dans des régénérateurs rotatifs.

Effect of fresh air purging on the efficiency of energy recovery from exhaust air in rotary regenerators.

Auteurs : WORSE-SCHMIDT P.

Type d'article : Article, Article de la RIF

Résumé

To prevent the carry-over of contaminated air to the fresh air in rotary heat regenerators, a small part of the incoming fresh air is used to purge the heat transfer matrix during its transfer from the hot to the cold zone. This purging causes a loss in the effectiveness of heat transfer in the regenerator. A simple numerical scheme employing heat transfer theory for elemental heat exchangers has been developed. This scheme was obtained by dividing the gas stream and the "stream" of matrix material into a number of flow channels, and the effect of fresh air purging has been calculated over a wide range of parameters. The results are presented numerically, graphically and in the form of approximate algebraic expressions.

Documents disponibles

Format PDF

Pages : 233-239

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Effect of fresh air purging on the efficiency of energy recovery from exhaust air in rotary regenerators.
  • Identifiant de la fiche : 30001887
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 14 - n. 4
  • Date d'édition : 07/1991

Liens


Voir d'autres articles du même numéro (6)
Voir la source