EFFET DE LA VARIATION DE L'ENTR'AXES DES TUBES DES DEUX BRANCHES D'UNE CANALISATION ENTERREE EN FORME DE U, SUR LE TRANSFERT DE CHALEUR D'UN CONDENSEUR.

EFFECT OF AXIAL SPACING VARIATION OF UNDERGROUND PIPE LOOP ON CONDENSER HEAT TRANSFER.

Résumé

ON A EFFECTUE UNE SIMULATION NUMERIQUE POUR ETUDIER L'EFFET DE LA VARIATION DE L'ENTR'AXES ENTRE DEUX < BRANCHES > D'UNE CANALISATION EN FORME DE U, SUR LA DISSIPATION DE LA CHALEUR, UTILISEE POUR LE REJET DE LA CHALEUR DU CONDENSEUR, DANS UNE POMPE A CHALEUR COUPLEE AU SOL, REFROIDIE PAR EAU, A BOUCLE FERMEE. ON A ETUDIE TROIS PROBLEMES SPECIFIQUES. EN CE QUI CONCERNE LE PREMIER, ON A UTILISE UN MODELE DE CONDUCTIVITE CONSTANTE, ET POUR LE SECOND, ON A CONSIDERE QU'IL EXISTAIT UNE RELATION LINEAIRE ENTRE LA CONDUCTIVITE DU SOL ET LA TEMPERATURE. EN SUPPOSANT QUE LES TEMPERATURES MOYENNES DE LA TERRE ET DE LA SURFACE EXTERIEURE DES < BRANCHES > ETAIENT CONSTANTES MAIS DIFFERENTES, ON A OBSERVE QU'UNE AUGMENTATION DE 20 % DANS LE TRANSFERT DE CHALEUR, PAR RAPPORT A LA DISPOSITION DE BASE DANS LAQUELLE LES TUBES SONT EN CONTACT L'UN AVEC L'AUTRE, POUVAIT ETRE OBTENUE SI L'ON MENAGEAIT UN ESPACE DE 0,18 M ENTRE LES BRANCHES ALLER ET RETOUR.

Détails

  • Titre original : EFFECT OF AXIAL SPACING VARIATION OF UNDERGROUND PIPE LOOP ON CONDENSER HEAT TRANSFER.
  • Identifiant de la fiche : 1989-2447
  • Langues : Anglais
  • Date d'édition : 1988
  • Source : Source : ASHRAE Trans.
    vol. 94; n. 2; 46-56; 5 fig.; 1 tabl.; 6 ref.