EFFETS DE DIFFERENTES CONFIGURATIONS DES AILETTES SUR LA PERFORMANCE D'ECHANGEURS DE CHALEUR A TUBES AILETES, DANS DES CONDITIONS DE GIVRAGE.

THE EFFECTS OF DIFFERENT FIN CONFIGURATIONS ON THE PERFORMANCE OF FINNED-TUBE HEAT EXCHANGES UNDER FROSTING CONDITIONS.

Résumé

ON A ETUDIE EXPERIMENTALEMENT LES EFFETS DE DIFFERENTES CONFIGURATIONS DES AILETTES SUR LA PERFORMANCE D'ECHANGEURS DE CHALEUR A TUBES AILETES, EN PRESENCE DE GIVRE, ET POUR DIFFERENTES VALEURS D'HUMIDITE DE L'AIR ET DE PAS DES AILETTES. LES TENDANCES D'ACCUMULATION DE GIVRE ET DE CHUTE DE PRESSION DU COTE DE L'AIR ONT CONFIRME LES OBSERVATIONS DEJA CONTENUES DANS LA BIBLIOGRAPHIE. CEPENDANT, LE COEFFICIENT DE TRANSFERT DE CHALEUR SENSIBLE A ETE PRESQUE CONSTANT PENDANT LES ESSAIS. ON A OBSERVE DES TENDANCES SEMBLABLES AVEC L'ABAISSEMENT DE L'ENTHALPIE ET L'EFFICACITE DE L'ECHANGEUR DECHALEUR, CE QUI CONFIRME QUE, POUR DES DUREES DE FONCTIONNEMENT INFERIEURES A UNE HEURE ET POUR LES CONDITIONS EXPERIMENTALES DONNEES, ON NE NOTE PAS DE VERITABLE DIMINUTION DE LA PERFORMANCE DU FAIT DU GIVRE.

Détails

  • Titre original : THE EFFECTS OF DIFFERENT FIN CONFIGURATIONS ON THE PERFORMANCE OF FINNED-TUBE HEAT EXCHANGES UNDER FROSTING CONDITIONS.
  • Identifiant de la fiche : 1992-0547
  • Langues : Anglais
  • Date d'édition : 1990
  • Source : Source : ASHRAE Trans.
    vol. 96; n. 2; 439-444; 13 fig.; 12 ref.