Effets de la lubrification sur l'ébullition de R123 et de R134a en écoulement sur un faisceau de tubes à ailettes forgées.
Effects of oil on boiling R123 and R134a flowing normal to an integral-finned tube bundle.
Auteurs : TATARA R. A., PAYVAR P.
Résumé
Local, experimental heat transfer coefficients have been measured for boiling refrigerant flowing up and across a tube bundle segment representing a full flooded evaporator tube bundle, R123 and R134a data with 26 fins per inch (1024 fins per meter) tubes have been obtained. The performance of R22 without oil has also been determined. Local tube and bulk fluid temperatures were measured directly by thermocouples to calculate the refrigerant-side heat transfer coefficients. The bundle segment saturation temperature set point (taken at the top of the tube bundle) is 4.4 °C.
Détails
- Titre original : Effects of oil on boiling R123 and R134a flowing normal to an integral-finned tube bundle.
- Identifiant de la fiche : 2000-1763
- Langues : Anglais
- Source : ASHRAE Transactions. 1999 Winter Meeting, Chicago, Illinois + CD-ROM.
- Date d'édition : 1999
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (54)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HCFC;
HFC;
Transfert de masse;
Lubrifiants - Mots-clés : R134a; Tube ailette; Mesure; Lubrifiant; Transfert de chaleur; R123; Mélange; Évaporateur; Échangeur multitubulaire; Frigorigène; Ébullition
-
Impacto de aditivos en lubricantes sobre la tra...
- Auteurs : KEDZIERSKI M. A.
- Date : 05/2007
- Langues : Espagnol
- Source : IIF-IIR/Frío Calor Aire acond. - vol. 35 - n. 392
- Formats : PDF
Voir la fiche
-
Experimental study on condensation heat transfe...
- Auteurs : INOUE N., KIRIYAMA T., TAKAHASHI H.
- Date : 21/08/2011
- Langues : Anglais
- Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
Voir la fiche
-
Effects of oil on boiling of replacement refrig...
- Auteurs : TATARA R. A., PAYVAR P.
- Date : 2000
- Langues : Anglais
- Source : ASHRAE Transactions. 2000 Winter Meeting, Dallas, Texas + CD-ROM.
Voir la fiche
-
Experimental measurements for condensation of d...
- Auteurs : HONDA H., TAKAMATSU H., TAKATA N.
- Date : 12/1999
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 22 - n. 8
- Formats : PDF
Voir la fiche
-
POOL BOILING DATA FOR FIVE REFRIGERANTS ON THRE...
- Auteurs : WEBB R. L., PAIS C.
- Date : 1991
- Langues : Anglais
Voir la fiche